Cathodic Protection Reference Cells: Purpose and Measurement

Cathodic protection reference cells are essential components in corrosion control systems, serving as stable electrochemical benchmarks for monitoring and maintaining the effectiveness of cathodic protection installations. These specialized devices enable precise measurement of structure-to-electrolyte potentials, ensuring optimal protection against corrosion in pipelines, storage tanks, and other metallic infrastructure.

An Overview of Cathodic Protection Potential Measurement

What is the Purpose of Cathodic Protection Reference Cells?

Reference cells serve as the foundation for accurate potential measurements in cathodic protection systems. Their primary purposes include:

  • Establishing Stable Reference Potential: Unlike metallic structures that change potential, reference cells maintain a consistent electrochemical potential regardless of current flow.
  • Monitoring Protection Levels: Engineers use reference cells to verify that protected structures achieve and maintain adequate protection criteria (typically -850mV vs. Cu/CuSO4 for steel).
  • System Diagnostics: Regular measurements help identify system failures, coating deterioration, or inadequate protection before visible corrosion occurs.
  • Compliance Documentation: Reference cell measurements provide verifiable data for regulatory compliance and asset management programs.

Common Types of Reference Cells

Different environments and applications require specific reference cell types, each offering unique advantages for cathodic protection monitoring:

Copper/Copper Sulfate (Cu/CuSO4) Reference Cells

The most widely used reference cell in buried and submerged applications. Consisting of copper immersed in saturated copper sulfate solution (+0.318V vs. SHE), these cells offer excellent long-term stability, wide temperature range (-10°C to 60°C), and low maintenance requirements. Ideal for pipeline surveys, tank bottoms, and permanent monitoring installations. Cost-effective and readily available, Cu/CuSO4 cells remain the industry standard for most soil environments.

Copper–copper(II) sulfate electrode - Wikipedia

Silver/Silver Chloride (Ag/AgCl) Reference Cells

Perfect for marine and seawater applications (+0.197V vs. SHE). Silver/silver chloride cells perform exceptionally well in high-chloride environments where Cu/CuSO4 cells may fail. Temperature stable from -20°C to 80°C, making them ideal for offshore platforms, marine structures, and seawater intake systems. Higher initial cost but superior durability in harsh saltwater conditions.

Portable Silver/Silver Chloride Reference Electrode - Jennings Anodes UK

How to Measure Cathodic Protection with Reference Cells

Proper measurement technique ensures accurate assessment of cathodic protection effectiveness:

  • Equipment Setup: Connect high-impedance voltmeter (>10 megohm input) between reference cell and protected structure. Ensure clean electrical connections and proper grounding.
  • Cell Preparation: Check reference cell electrolyte level, verify porous plug is moist, and establish good soil/electrolyte contact.
  • Measurement Procedure: Place reference cell directly above structure (buried systems) or at specified distance (submerged structures). Allow readings to stabilize (typically 30-60 seconds) before recording.
  • IR Drop Correction: For accurate structure potential, apply instant-off measurements or use voltage interruption techniques to eliminate IR drop effects.
  • Documentation: Record date, time, location, temperature, cell type, and reading. Map measurement points for trend analysis.

Practical Tips for Reference Cell Use

Maximize accuracy and longevity with these best practices:

  • Regular Calibration: Verify reference cell potential against known standards annually. Replace cells showing drift >10mV.
  • Proper Storage: Store cells upright with caps sealed to prevent electrolyte evaporation. Keep terminals clean and corrosion-free.
  • Temperature Compensation: Apply correction factors for temperature variations. Cu/CuSO4 cells shift approximately +0.9mV/°C.
  • Contact Resistance: Ensure good electrolyte contact by wetting porous plugs before measurements. Poor contact causes erratic readings.
  • Safety Considerations: Use appropriate PPE when handling reference cells. Some electrolytes are toxic or corrosive.

External References

For further reading on cathodic protection reference cells, consult these authoritative sources: